Spec Builder for Non-Metallic Pipes

Narrow down using the filters below. Add the right system(s) to your quote.

Showing 56 of 56 systems
#UL ReferenceProducts UsedBOQ Spec TextUOMDia (mm)Apply ₹Supply ₹Total ₹
1C-AJ-2305CP 648E Wrap Strip, FS-ONE Max,Retaining Collar
Providing UL-listed firestop system C-AJ-2305 for 8" PVC/CPVC pipe penetrations through 4-1/2" thick concrete floor/wall assemblies. The system shall provide 2-hour fire rating, tested to ASTM E814 / …
Each2031,46015,791.0117,735.01
2C-AJ-2305CP 648E Wrap Strip, FS-ONE Max,Retaining Collar
Providing UL-listed firestop system C-AJ-2305 for 8" PVC/CPVC pipe penetrations through 4-1/2" thick concrete floor/ wall assemblies. The system shall provide 2-hour fire rating, tested to ASTM E814 /…
Each2031,46015,791.0117,735.01
3C-AJ-2336CP 648E Wrap Strip, FS-ONE Max,Retaining Collar
Providing UL-listed firestop system C-AJ-2336 for 4" PVC/ABS/CPVC/FRPP pipe penetrations through 4-1/2" thick concrete wall/floor assemblies. The system shall provide 3-hour fire rating, tested to AST…
Each1023,785.02
4C-AJ-2336CP 648E Wrap Strip, FS-ONE Max,Hilti Retaining Collar
Providing UL-listed firestop system C-AJ-2336 for 4" PVC/ABS/CPVC/FRPP pipe penetrations through 4-1/2" thick concrete wall/floor assemblies. The system shall provide 3-hour fire rating, tested to AST…
Nos1023,785.02
5C-AJ-2336CP 648E Wrap Strip, FS-ONE Max,Hilti Retaining Collar
Providing UL-listed firestop system C-AJ-2336 for 4" PVC/ABS/CPVC/FRPP pipe penetrations through 4-1/2" thick concrete wall/floor assemblies. The system shall provide 3-hour fire rating, tested to AST…
Nos1023,785.02
6C-AJ-2336CP 648E Wrap Strip, FS-ONE Max,Hilti Retaining Collar
Providing UL-listed firestop system C-AJ-2336 for 4" PVC/ABS/CPVC/FRPP pipe penetrations through 4-1/2" thick concrete wall/floor assemblies. The system shall provide 3-hour fire rating, tested to AST…
Nos1023,785.02
7C-AJ-2342CP 648E Wrap Strip, FS-ONE Max
Provide UL-listed firestop system C-AJ-2342 for four 2-1/2" PVC/ABS/CPVC/FRPP pipe penetrations through 4-1/2" thick concrete wall/floor assemblies, achieving a 3-hour fire rating (minimum 2-hour asse…
Nos102377.53,882.024,351.51
8C-AJ-2342CP 648E Wrap Strip, FS-ONE Max
Provide UL-listed firestop system C-AJ-2342 for four 2-1/2" PVC/ABS/CPVC/FRPP pipe penetrations through 4-1/2" thick concrete wall/floor assemblies, achieving a 3-hour fire rating (minimum 2-hour asse…
Nos102377.53,882.024,351.51
9C-AJ-2342CP 648E Wrap Strip, FS-ONE Max
Provide UL-listed firestop system C-AJ-2342 for four 2-1/2" PVC/ABS/CPVC/FRPP pipe penetrations through 4-1/2" thick concrete wall/floor assemblies, achieving a 3-hour fire rating (minimum 2-hour asse…
Nos102377.53,882.024,351.51
10C-AJ-2342CP 648E Wrap Strip, FS-ONE Max
Provide UL-listed firestop system C-AJ-2342 for four 2-1/2" PVC/ABS/CPVC/FRPP pipe penetrations through 4-1/2" thick concrete wall/floor assemblies, achieving a 3-hour fire rating (minimum 2-hour asse…
Nos102377.53,882.024,351.51
11C-AJ-2343CP 648E Wrap Strip, FS-ONE Max,Hilti Retaining Collar
Provide UL-listed firestop system C-AJ-2343 for 4" PVC/CPVC/ABS/FRPP pipe penetrations through 4-1/2" thick wall/floor assemblies, rated for 3 hours per ASTM E814 / UL 1479. Opening size shall be 4-1/…
Nos1023,785.02
12C-AJ-2343CP 648E Wrap Strip, FS-ONE Max,Hilti Retaining Collar
Provide UL-listed firestop system C-AJ-2343 for 4" PVC/CPVC/ABS/FRPP pipe penetrations through 4-1/2" thick wall/floor assemblies, rated for 3 hours per ASTM E814 / UL 1479. Opening size shall be 4-1/…
Nos1023,785.02
13C-AJ-2343CP 648E Wrap Strip, FS-ONE Max,Hilti Retaining Collar
Provide UL-listed firestop system C-AJ-2343 for 4" PVC/CPVC/ABS/FRPP pipe penetrations through 4-1/2" thick wall/floor assemblies, rated for 3 hours per ASTM E814 / UL 1479. Opening size shall be 4-1/…
Nos1023,785.02
14C-AJ-2343CP 648E Wrap Strip, FS-ONE Max,Hilti Retaining Collar
Provide UL-listed firestop system C-AJ-2343 for 4" PVC/CPVC/ABS/FRPP pipe penetrations through 4-1/2" thick wall/floor assemblies, rated for 3 hours per ASTM E814 / UL 1479. Opening size shall be 4-1/…
Nos1023,785.02
15C-AJ-2371CP 648E Wrap Strip, FS-ONE Max,Hilti Retaining Collar
Provide UL-listed firestop system C-AJ-2371 for 6" PVC/CPVC/ABS/FRPP pipe penetrations through 4-1/2" thick wall/floor assemblies, rated for 3 hours per ASTM E814 / UL 1479. Opening size shall be 7" w…
Nos1528307,624.238,506.23
16C-AJ-2371CP 648E Wrap Strip, FS-ONE Max,Hilti Retaining Collar
Provide UL-listed firestop system C-AJ-2371 for 6" PVC/CPVC/ABS/FRPP pipe penetrations through 4-1/2" thick wall/floor assemblies, rated for 3 hours per ASTM E814 / UL 1479. Opening size shall be 7" w…
Nos1528307,624.238,506.23
17C-AJ-2371CP 648E Wrap Strip, FS-ONE Max,Hilti Retaining Collar
Provide UL-listed firestop system C-AJ-2371 for 6" PVC/CPVC/ABS/FRPP pipe penetrations through 4-1/2" thick wall/floor assemblies, rated for 3 hours per ASTM E814 / UL 1479. Opening size shall be 7" w…
Nos1528307,624.238,506.23
18C-AJ-2371CP 648E Wrap Strip, FS-ONE Max,Hilti Retaining Collar
Provide UL-listed firestop system C-AJ-2371 for 6" PVC/CPVC/ABS/FRPP pipe penetrations through 4-1/2" thick wall/floor assemblies, rated for 3 hours per ASTM E814 / UL 1479. Opening size shall be 7" w…
Nos1528307,624.238,506.23
19C-AJ-2393CP 648E Wrap Strip, FS-ONE Max
Provide UL-listed firestop system C-AJ-2393 for 4" PVC/CPVC pipe penetrations through 4-1/2" thick floor assemblies and 5" thick wall assemblies, rated for 2 hours per ASTM E814 / UL 1479. Opening siz…
Nos1023,785.02
20C-AJ-2393CP 648E Wrap Strip, FS-ONE Max
Provide UL-listed firestop system C-AJ-2393 for 4" PVC/CPVC pipe penetrations through 4-1/2" thick floor assemblies and 5" thick wall assemblies, rated for 2 hours per ASTM E814 / UL 1479. Opening siz…
Nos1023,785.02
21C-AJ-2409CP 648E Wrap Strip,Hilti Retaining Collar, CP-620 Fire Foam
Providing UL-listed firestop system C-AJ-2409 for 10" Flame Retardant Polypropylene (FRPP) pipe penetrations through 4-1/2" thick wall/floor assemblies. The system shall provide a 3-hour fire rating, …
Nos25430,844.33
22C-AJ-2419CP 648E Wrap Strip, FS-ONE Max
Providing UL-listed firestop system C-AJ-2419 for 4" PVC/ABS/CPVC pipe penetrations through 4-1/2" thick floor assemblies and 5" thick wall assemblies. The system shall provide a 3-hour fire rating, t…
Nos1023,785.02
23C-AJ-2419CP 648E Wrap Strip, FS-ONE Max
Providing UL-listed firestop system C-AJ-2419 for 4" PVC/ABS/CPVC pipe penetrations through 4-1/2" thick floor assemblies and 5" thick wall assemblies. The system shall provide a 3-hour fire rating, t…
Nos1023,785.02
24C-AJ-2419CP 648E Wrap Strip, FS-ONE Max
Providing UL-listed firestop system C-AJ-2419 for 4" diameter PVC/ABS/CPVC pipe penetrations through 4-1/2" thick floor assemblies and 5" thick wall assemblies. The system shall provide a 3-hour fire …
Nos1023,785.02
25C-AJ-2420CP 648E Wrap Strip,Hilti Retaining Collar, FS-ONE Max
Provide UL-Listed firestopping for 10" diameter PVC/CPVC pipe penetrations through 3-hour rated concrete or masonry wall/floor assemblies. The opening shall be a nominal 14" diameter with a 1/4"-1/2" …
Nos25425,116.88
26C-AJ-2420CP 648E Wrap Strip,Hilti Retaining Collar, FS-ONE Max
Provide UL-Listed firestopping for 10" diameter PVC/CPVC pipe penetrations through 3-hour rated concrete or masonry wall/floor assemblies. The opening shall be a nominal 14" diameter with a 1/4"-1/2" …
Nos25425,116.88
27C-AJ-2420CP 648E Wrap Strip,Hilti Retaining Collar, FS-ONE Max
Provide UL-Listed firestopping for 10" diameter PVC/CPVC pipe penetrations through 3-hour rated concrete or masonry wall/floor assemblies. The opening shall be a nominal 14" diameter with a 1/4"-1/2" …
Nos30423,632.27
28C-AJ-2420CP 648E Wrap Strip,Hilti Retaining Collar, FS-ONE Max
Provide UL-Listed firestopping for 10" diameter PVC/CPVC pipe penetrations through 3-hour rated concrete or masonry wall/floor assemblies. The opening shall be a nominal 14" diameter with a 1/4"-1/2" …
Nos30423,632.27
29C-AJ-2567FS-ONE Max
Provide UL-listed firestop system C-AJ-2567 for 2" PVC/CPVC/RNC/PEX/PP-R pipe penetrations through 4-1/2" thick concrete floor assemblies and 5" thick wall assemblies, achieving a 2-hour fire rating p…
Nos51266.75
30C-AJ-2567FS-ONE Max
Provide UL-listed firestop system C-AJ-2567 for 2" PVC/CPVC/RNC/PEX/PP-R pipe penetrations through 4-1/2" thick concrete floor assemblies and 5" thick wall assemblies, achieving a 2-hour fire rating p…
Nos51266.75
31C-AJ-2567FS-ONE Max
Provide UL-listed firestop system C-AJ-2567 for two 2" PVC/CPVC/RNC/PEX/PP-R pipe penetrations through 4-1/2" thick concrete floor assemblies and 5" thick wall assemblies, achieving a 2-hour fire rati…
Nos51266.75
32C-AJ-2567FS-ONE Max
Provide UL-listed firestop system C-AJ-2567 for two 2" PVC/CPVC/RNC/PEX/PP-R pipe penetrations through 4-1/2" thick concrete floor assemblies and 5" thick wall assemblies, achieving a 2-hour fire rati…
Nos51266.75
33C-AJ-2567FS-ONE Max
Provide UL-listed firestop system C-AJ-2567 for two 2" PVC/CPVC/RNC/PEX/PP-R pipe penetrations through 4-1/2" thick concrete floor assemblies and 5" thick wall assemblies, achieving a 2-hour fire rati…
Nos51266.75
34C-AJ-2599CP 648E Wrap Strip, FS-ONE Max,Hilti Retaining Collar
Providing UL-listed firestop system C-AJ-2599 for 4" PP pipe penetrations through 5" thick concrete wall assemblies and 4-1/2" thick floor assemblies. The system shall provide 2-hour fire rating, test…
Nos1274,880.07
35C-AJ-2599CP 648E Wrap Strip, FS-ONE Max,Hilti Retaining Collar
Providing UL-listed firestop system C-AJ-2599 for 4" PP pipe penetrations through 5" thick concrete wall assemblies and 4-1/2" thick floor assemblies. The system shall provide 2-hour fire rating, test…
Nos1024,245.76
36C-AJ-2600CP 643N Firestop Collar, FS-ONE Max
Providing UL-listed firestop system C-AJ-2600 for 2" PP pipe penetrations through 5" thick concrete wall assemblies and 4-1/2" thick floor assemblies. The system shall provide 2-hour fire rating, test…
Nos513,051.75
37C-AJ-2600CP 643N Firestop Collar, FS-ONE Max
Providing UL-listed firestop system C-AJ-2600 for 2" PP pipe penetrations through 5" thick concrete wall assemblies and 4-1/2" thick floor assemblies. The system shall provide 2-hour fire rating, test…
Nos10210,530.75
38C-AJ-2630CP 643N Firestop Collar,CP 637 Firestop Mortar
Providing UL-listed firestop system C-AJ-2630 for 4" PVC/CPVC/ABS/FRPP pipe penetrations through 2-1/2" thick concrete wall/floor assemblies. The system shall provide 2-hour fire rating, tested to AST…
Nos10210,771.53
39C-AJ-2630CP 643N Firestop Collar,CP 637 Firestop Mortar
Providing UL-listed firestop system C-AJ-2630 for 4" PVC/CPVC/ABS/FRPP pipe penetrations through 2-1/2" thick concrete wall/floor assemblies. The system shall provide 2-hour fire rating, tested to AST…
Nos10210,771.53
40C-AJ-2630CP 643N Firestop Collar,CP 637 Firestop Mortar
Providing UL-listed firestop system C-AJ-2630 for 4" PVC/CPVC/ABS/FRPP pipe penetrations through 2-1/2" thick concrete wall/floor assemblies. The system shall provide 2-hour fire rating, tested to AST…
Nos10210,771.53
41C-AJ-2630CP 643N Firestop Collar,CP 637 Firestop Mortar
Providing UL-listed firestop system C-AJ-2630 for 4" PVC/CPVC/ABS/FRPP pipe penetrations through 2-1/2" thick concrete wall/floor assemblies. The system shall provide 2-hour fire rating, tested to AST…
Nos10210,771.53
42C-AJ-2647FS-ONE Max
Providing UL-listed firestop system C-AJ-2647 for 2" PVC/CPVC/RNC/ENT/PEX pipe penetrations through 3-1/2" thick concrete wall assemblies. The system shall provide 2-hour fire rating, tested to ASTM E…
Nos5052315.25367.25
43C-AJ-2647FS-ONE Max
Providing UL-listed firestop system C-AJ-2647 for 2" PVC/CPVC/RNC/ENT/PEX pipe penetrations through 3-1/2" thick concrete wall assemblies. The system shall provide 2-hour fire rating, tested to ASTM E…
nos5052315.25367.25
44C-AJ-2647FS-ONE Max
Providing UL-listed firestop system C-AJ-2647 for 2" PVC/CPVC/RNC/ENT/PEX pipe penetrations through 3-1/2" thick concrete wall assemblies. The system shall provide 2-hour fire rating, tested to ASTM E…
nos5052315.25367.25
45C-AJ-2647FS-ONE Max
Providing UL-listed firestop system C-AJ-2647 for 2" PVC/CPVC/RNC/ENT/PEX pipe penetrations through 3-1/2" thick concrete wall assemblies. The system shall provide 2-hour fire rating, tested to ASTM E…
nos5052315.25367.25
46C-AJ-2647FS-ONE Max
Providing UL-listed firestop system C-AJ-2647 for 2" PVC/CPVC/RNC/ENT/PEX pipe penetrations through 3-1/2" thick concrete wall assemblies. The system shall provide 2-hour fire rating, tested to ASTM E…
nos2552315.25367.25
47C-AJ-2677CP648E Wrap Strip, FS-ONE Max
Providing UL-listed firestop system C-AJ-2677 for Providing UL-listed firestop system C-AJ-2647 for 2" PVC/CPVC/RNC/ENT/PEX pipe penetrations through 3-1/2" thick concrete wall assemblies. The system …
Nos51924.63
48C-AJ-2700FS-ONE Max
Provide UL-listed firestop system for C-AJ-2700 1-1/4" PP pipe penetrations through 4-1/2" thick concrete wall assemblies and 6" thick floor assemblies, achieving a 2-hour F-rating per ASTM E814 / UL …
nos3260363.75423.75
49C-AJ-2700FS-ONE Max
Provide UL-listed firestop system for C-AJ-2700 1" PP pipe penetrations through 4-1/2" thick concrete wall assemblies and 6" thick floor assemblies, achieving a 2-hour F-rating per ASTM E814 / UL 1479…
Nos25315.25
50C-AJ-2700FS-ONE Max
Provide UL-listed firestop system for C-AJ-2700 3/4" PP pipe penetrations through 4-1/2" thick concrete wall assemblies and 6" thick floor assemblies, achieving a 2-hour F-rating per ASTM E814 / UL 14…
Nos19266.75
51C-AJ-2770CP 648E Wrap Strip,FS-ONE Max
Provide UL-listed firestop system C-AJ-2770 for 6" PP-R pipe through 4-1/2" thick Wall/floor, achieving 2 hour fire rating per ASTM E814 / UL 1479.Opening size shall be 8" with 1/2"-3/8" annular space…
Nos152
52C-AJ-2770CP 648E Wrap Strip,FS-ONE Max
Provide UL-listed firestop system C-AJ-2770 for 4" PP-R pipe through 4-1/2" thick Wall/floor, achieving 2 hour fire rating per ASTM E814 / UL 1479.Opening size shall be 8" with 1/2"-3/8" annular space…
Nos102
53C-AJ-2831CP 648E Wrap Strip,FS-ONE Max,Hilti Retaining Collar
Provide UL-listed firestop system C-AJ-2831 for 6" PP-R pipe through 4-1/2" thick wall/floor, achieving 2 hour fire rating per ASTM E814 / UL 1479. Opening size shall be 7" with 0"-1/2" annular space,…
Nos1528,618.48
54C-AJ-2885Hilti CFS-COS Firestop Composite Sheet, CP 619T Firestop Putty Roll, CP 617 Firestop Putty Pad or FS-ONE Max,CP 643N
Provide UL-listed firestop system C-AJ-2885 for 6" PVC/CPVC/RNC pipe through wall/floor thick 4-1/2", achieving 2-hour fire rating per ASTM E814 / UL 1479. Opening size shall be 30" with min 0" annula…
nos1525,806.4554,856.9361,541.38
55C-AJ-2885Hilti CFS-COS Firestop Composite Sheet, CP 619T Firestop Putty Roll, CP 617 Firestop Putty Pad or FS-ONE Max,CP 643N
Provide UL-listed firestop system C-AJ-2885 for 6" PVC/CPVC/RNC pipe through wall/floor thick 4-1/2", achieving 2-hour fire rating per ASTM E814 / UL 1479. Opening size shall be 30" with min 0" annula…
nos1525,806.4554,856.9361,541.38
56C-AJ-2885Hilti CFS-COS Firestop Composite Sheet, CP 619T Firestop Putty Roll, CP 617 Firestop Putty Pad or FS-ONE Max,CP 643N
Provide UL-listed firestop system C-AJ-2885 for 6" PVC/CPVC/RNC pipe through wall/floor thick 4-1/2", achieving 2-hour fire rating per ASTM E814 / UL 1479. Opening size shall be 30" with min 0" annula…
nos1525,806.4554,856.9361,541.38