Spec Builder for Non-Metallic Pipes
Narrow down using the filters below. Add the right system(s) to your quote.
Showing 56 of 56 systems
| # | UL Reference | Products Used | BOQ Spec Text | UOM | Dia (mm) | Apply ₹ | Supply ₹ | Total ₹ | |
|---|---|---|---|---|---|---|---|---|---|
| 1 | C-AJ-2305 | CP 648E Wrap Strip, FS-ONE Max,Retaining Collar | Providing UL-listed firestop system C-AJ-2305 for 8" PVC/CPVC pipe penetrations through 4-1/2" thick concrete floor/wall assemblies. The system shall provide 2-hour fire rating, tested to ASTM E814 / … | Each | 203 | 1,460 | 15,791.01 | 17,735.01 | |
| 2 | C-AJ-2305 | CP 648E Wrap Strip, FS-ONE Max,Retaining Collar | Providing UL-listed firestop system C-AJ-2305 for 8" PVC/CPVC pipe penetrations through 4-1/2" thick concrete floor/ wall assemblies. The system shall provide 2-hour fire rating, tested to ASTM E814 /… | Each | 203 | 1,460 | 15,791.01 | 17,735.01 | |
| 3 | C-AJ-2336 | CP 648E Wrap Strip, FS-ONE Max,Retaining Collar | Providing UL-listed firestop system C-AJ-2336 for 4" PVC/ABS/CPVC/FRPP pipe penetrations through 4-1/2" thick concrete wall/floor assemblies. The system shall provide 3-hour fire rating, tested to AST… | Each | 102 | — | 3,785.02 | — | |
| 4 | C-AJ-2336 | CP 648E Wrap Strip, FS-ONE Max,Hilti Retaining Collar | Providing UL-listed firestop system C-AJ-2336 for 4" PVC/ABS/CPVC/FRPP pipe penetrations through 4-1/2" thick concrete wall/floor assemblies. The system shall provide 3-hour fire rating, tested to AST… | Nos | 102 | — | 3,785.02 | — | |
| 5 | C-AJ-2336 | CP 648E Wrap Strip, FS-ONE Max,Hilti Retaining Collar | Providing UL-listed firestop system C-AJ-2336 for 4" PVC/ABS/CPVC/FRPP pipe penetrations through 4-1/2" thick concrete wall/floor assemblies. The system shall provide 3-hour fire rating, tested to AST… | Nos | 102 | — | 3,785.02 | — | |
| 6 | C-AJ-2336 | CP 648E Wrap Strip, FS-ONE Max,Hilti Retaining Collar | Providing UL-listed firestop system C-AJ-2336 for 4" PVC/ABS/CPVC/FRPP pipe penetrations through 4-1/2" thick concrete wall/floor assemblies. The system shall provide 3-hour fire rating, tested to AST… | Nos | 102 | — | 3,785.02 | — | |
| 7 | C-AJ-2342 | CP 648E Wrap Strip, FS-ONE Max | Provide UL-listed firestop system C-AJ-2342 for four 2-1/2" PVC/ABS/CPVC/FRPP pipe penetrations through 4-1/2" thick concrete wall/floor assemblies, achieving a 3-hour fire rating (minimum 2-hour asse… | Nos | 102 | 377.5 | 3,882.02 | 4,351.51 | |
| 8 | C-AJ-2342 | CP 648E Wrap Strip, FS-ONE Max | Provide UL-listed firestop system C-AJ-2342 for four 2-1/2" PVC/ABS/CPVC/FRPP pipe penetrations through 4-1/2" thick concrete wall/floor assemblies, achieving a 3-hour fire rating (minimum 2-hour asse… | Nos | 102 | 377.5 | 3,882.02 | 4,351.51 | |
| 9 | C-AJ-2342 | CP 648E Wrap Strip, FS-ONE Max | Provide UL-listed firestop system C-AJ-2342 for four 2-1/2" PVC/ABS/CPVC/FRPP pipe penetrations through 4-1/2" thick concrete wall/floor assemblies, achieving a 3-hour fire rating (minimum 2-hour asse… | Nos | 102 | 377.5 | 3,882.02 | 4,351.51 | |
| 10 | C-AJ-2342 | CP 648E Wrap Strip, FS-ONE Max | Provide UL-listed firestop system C-AJ-2342 for four 2-1/2" PVC/ABS/CPVC/FRPP pipe penetrations through 4-1/2" thick concrete wall/floor assemblies, achieving a 3-hour fire rating (minimum 2-hour asse… | Nos | 102 | 377.5 | 3,882.02 | 4,351.51 | |
| 11 | C-AJ-2343 | CP 648E Wrap Strip, FS-ONE Max,Hilti Retaining Collar | Provide UL-listed firestop system C-AJ-2343 for 4" PVC/CPVC/ABS/FRPP pipe penetrations through 4-1/2" thick wall/floor assemblies, rated for 3 hours per ASTM E814 / UL 1479. Opening size shall be 4-1/… | Nos | 102 | — | 3,785.02 | — | |
| 12 | C-AJ-2343 | CP 648E Wrap Strip, FS-ONE Max,Hilti Retaining Collar | Provide UL-listed firestop system C-AJ-2343 for 4" PVC/CPVC/ABS/FRPP pipe penetrations through 4-1/2" thick wall/floor assemblies, rated for 3 hours per ASTM E814 / UL 1479. Opening size shall be 4-1/… | Nos | 102 | — | 3,785.02 | — | |
| 13 | C-AJ-2343 | CP 648E Wrap Strip, FS-ONE Max,Hilti Retaining Collar | Provide UL-listed firestop system C-AJ-2343 for 4" PVC/CPVC/ABS/FRPP pipe penetrations through 4-1/2" thick wall/floor assemblies, rated for 3 hours per ASTM E814 / UL 1479. Opening size shall be 4-1/… | Nos | 102 | — | 3,785.02 | — | |
| 14 | C-AJ-2343 | CP 648E Wrap Strip, FS-ONE Max,Hilti Retaining Collar | Provide UL-listed firestop system C-AJ-2343 for 4" PVC/CPVC/ABS/FRPP pipe penetrations through 4-1/2" thick wall/floor assemblies, rated for 3 hours per ASTM E814 / UL 1479. Opening size shall be 4-1/… | Nos | 102 | — | 3,785.02 | — | |
| 15 | C-AJ-2371 | CP 648E Wrap Strip, FS-ONE Max,Hilti Retaining Collar | Provide UL-listed firestop system C-AJ-2371 for 6" PVC/CPVC/ABS/FRPP pipe penetrations through 4-1/2" thick wall/floor assemblies, rated for 3 hours per ASTM E814 / UL 1479. Opening size shall be 7" w… | Nos | 152 | 830 | 7,624.23 | 8,506.23 | |
| 16 | C-AJ-2371 | CP 648E Wrap Strip, FS-ONE Max,Hilti Retaining Collar | Provide UL-listed firestop system C-AJ-2371 for 6" PVC/CPVC/ABS/FRPP pipe penetrations through 4-1/2" thick wall/floor assemblies, rated for 3 hours per ASTM E814 / UL 1479. Opening size shall be 7" w… | Nos | 152 | 830 | 7,624.23 | 8,506.23 | |
| 17 | C-AJ-2371 | CP 648E Wrap Strip, FS-ONE Max,Hilti Retaining Collar | Provide UL-listed firestop system C-AJ-2371 for 6" PVC/CPVC/ABS/FRPP pipe penetrations through 4-1/2" thick wall/floor assemblies, rated for 3 hours per ASTM E814 / UL 1479. Opening size shall be 7" w… | Nos | 152 | 830 | 7,624.23 | 8,506.23 | |
| 18 | C-AJ-2371 | CP 648E Wrap Strip, FS-ONE Max,Hilti Retaining Collar | Provide UL-listed firestop system C-AJ-2371 for 6" PVC/CPVC/ABS/FRPP pipe penetrations through 4-1/2" thick wall/floor assemblies, rated for 3 hours per ASTM E814 / UL 1479. Opening size shall be 7" w… | Nos | 152 | 830 | 7,624.23 | 8,506.23 | |
| 19 | C-AJ-2393 | CP 648E Wrap Strip, FS-ONE Max | Provide UL-listed firestop system C-AJ-2393 for 4" PVC/CPVC pipe penetrations through 4-1/2" thick floor assemblies and 5" thick wall assemblies, rated for 2 hours per ASTM E814 / UL 1479. Opening siz… | Nos | 102 | — | 3,785.02 | — | |
| 20 | C-AJ-2393 | CP 648E Wrap Strip, FS-ONE Max | Provide UL-listed firestop system C-AJ-2393 for 4" PVC/CPVC pipe penetrations through 4-1/2" thick floor assemblies and 5" thick wall assemblies, rated for 2 hours per ASTM E814 / UL 1479. Opening siz… | Nos | 102 | — | 3,785.02 | — | |
| 21 | C-AJ-2409 | CP 648E Wrap Strip,Hilti Retaining Collar, CP-620 Fire Foam | Providing UL-listed firestop system C-AJ-2409 for 10" Flame Retardant Polypropylene (FRPP) pipe penetrations through 4-1/2" thick wall/floor assemblies. The system shall provide a 3-hour fire rating, … | Nos | 254 | — | 30,844.33 | — | |
| 22 | C-AJ-2419 | CP 648E Wrap Strip, FS-ONE Max | Providing UL-listed firestop system C-AJ-2419 for 4" PVC/ABS/CPVC pipe penetrations through 4-1/2" thick floor assemblies and 5" thick wall assemblies. The system shall provide a 3-hour fire rating, t… | Nos | 102 | — | 3,785.02 | — | |
| 23 | C-AJ-2419 | CP 648E Wrap Strip, FS-ONE Max | Providing UL-listed firestop system C-AJ-2419 for 4" PVC/ABS/CPVC pipe penetrations through 4-1/2" thick floor assemblies and 5" thick wall assemblies. The system shall provide a 3-hour fire rating, t… | Nos | 102 | — | 3,785.02 | — | |
| 24 | C-AJ-2419 | CP 648E Wrap Strip, FS-ONE Max | Providing UL-listed firestop system C-AJ-2419 for 4" diameter PVC/ABS/CPVC pipe penetrations through 4-1/2" thick floor assemblies and 5" thick wall assemblies. The system shall provide a 3-hour fire … | Nos | 102 | — | 3,785.02 | — | |
| 25 | C-AJ-2420 | CP 648E Wrap Strip,Hilti Retaining Collar, FS-ONE Max | Provide UL-Listed firestopping for 10" diameter PVC/CPVC pipe penetrations through 3-hour rated concrete or masonry wall/floor assemblies. The opening shall be a nominal 14" diameter with a 1/4"-1/2" … | Nos | 254 | — | 25,116.88 | — | |
| 26 | C-AJ-2420 | CP 648E Wrap Strip,Hilti Retaining Collar, FS-ONE Max | Provide UL-Listed firestopping for 10" diameter PVC/CPVC pipe penetrations through 3-hour rated concrete or masonry wall/floor assemblies. The opening shall be a nominal 14" diameter with a 1/4"-1/2" … | Nos | 254 | — | 25,116.88 | — | |
| 27 | C-AJ-2420 | CP 648E Wrap Strip,Hilti Retaining Collar, FS-ONE Max | Provide UL-Listed firestopping for 10" diameter PVC/CPVC pipe penetrations through 3-hour rated concrete or masonry wall/floor assemblies. The opening shall be a nominal 14" diameter with a 1/4"-1/2" … | Nos | 304 | — | 23,632.27 | — | |
| 28 | C-AJ-2420 | CP 648E Wrap Strip,Hilti Retaining Collar, FS-ONE Max | Provide UL-Listed firestopping for 10" diameter PVC/CPVC pipe penetrations through 3-hour rated concrete or masonry wall/floor assemblies. The opening shall be a nominal 14" diameter with a 1/4"-1/2" … | Nos | 304 | — | 23,632.27 | — | |
| 29 | C-AJ-2567 | FS-ONE Max | Provide UL-listed firestop system C-AJ-2567 for 2" PVC/CPVC/RNC/PEX/PP-R pipe penetrations through 4-1/2" thick concrete floor assemblies and 5" thick wall assemblies, achieving a 2-hour fire rating p… | Nos | 51 | — | 266.75 | — | |
| 30 | C-AJ-2567 | FS-ONE Max | Provide UL-listed firestop system C-AJ-2567 for 2" PVC/CPVC/RNC/PEX/PP-R pipe penetrations through 4-1/2" thick concrete floor assemblies and 5" thick wall assemblies, achieving a 2-hour fire rating p… | Nos | 51 | — | 266.75 | — | |
| 31 | C-AJ-2567 | FS-ONE Max | Provide UL-listed firestop system C-AJ-2567 for two 2" PVC/CPVC/RNC/PEX/PP-R pipe penetrations through 4-1/2" thick concrete floor assemblies and 5" thick wall assemblies, achieving a 2-hour fire rati… | Nos | 51 | — | 266.75 | — | |
| 32 | C-AJ-2567 | FS-ONE Max | Provide UL-listed firestop system C-AJ-2567 for two 2" PVC/CPVC/RNC/PEX/PP-R pipe penetrations through 4-1/2" thick concrete floor assemblies and 5" thick wall assemblies, achieving a 2-hour fire rati… | Nos | 51 | — | 266.75 | — | |
| 33 | C-AJ-2567 | FS-ONE Max | Provide UL-listed firestop system C-AJ-2567 for two 2" PVC/CPVC/RNC/PEX/PP-R pipe penetrations through 4-1/2" thick concrete floor assemblies and 5" thick wall assemblies, achieving a 2-hour fire rati… | Nos | 51 | — | 266.75 | — | |
| 34 | C-AJ-2599 | CP 648E Wrap Strip, FS-ONE Max,Hilti Retaining Collar | Providing UL-listed firestop system C-AJ-2599 for 4" PP pipe penetrations through 5" thick concrete wall assemblies and 4-1/2" thick floor assemblies. The system shall provide 2-hour fire rating, test… | Nos | 127 | — | 4,880.07 | — | |
| 35 | C-AJ-2599 | CP 648E Wrap Strip, FS-ONE Max,Hilti Retaining Collar | Providing UL-listed firestop system C-AJ-2599 for 4" PP pipe penetrations through 5" thick concrete wall assemblies and 4-1/2" thick floor assemblies. The system shall provide 2-hour fire rating, test… | Nos | 102 | — | 4,245.76 | — | |
| 36 | C-AJ-2600 | CP 643N Firestop Collar, FS-ONE Max | Providing UL-listed firestop system C-AJ-2600 for 2" PP pipe penetrations through 5" thick concrete wall assemblies and 4-1/2" thick floor assemblies. The system shall provide 2-hour fire rating, test… | Nos | 51 | — | 3,051.75 | — | |
| 37 | C-AJ-2600 | CP 643N Firestop Collar, FS-ONE Max | Providing UL-listed firestop system C-AJ-2600 for 2" PP pipe penetrations through 5" thick concrete wall assemblies and 4-1/2" thick floor assemblies. The system shall provide 2-hour fire rating, test… | Nos | 102 | — | 10,530.75 | — | |
| 38 | C-AJ-2630 | CP 643N Firestop Collar,CP 637 Firestop Mortar | Providing UL-listed firestop system C-AJ-2630 for 4" PVC/CPVC/ABS/FRPP pipe penetrations through 2-1/2" thick concrete wall/floor assemblies. The system shall provide 2-hour fire rating, tested to AST… | Nos | 102 | — | 10,771.53 | — | |
| 39 | C-AJ-2630 | CP 643N Firestop Collar,CP 637 Firestop Mortar | Providing UL-listed firestop system C-AJ-2630 for 4" PVC/CPVC/ABS/FRPP pipe penetrations through 2-1/2" thick concrete wall/floor assemblies. The system shall provide 2-hour fire rating, tested to AST… | Nos | 102 | — | 10,771.53 | — | |
| 40 | C-AJ-2630 | CP 643N Firestop Collar,CP 637 Firestop Mortar | Providing UL-listed firestop system C-AJ-2630 for 4" PVC/CPVC/ABS/FRPP pipe penetrations through 2-1/2" thick concrete wall/floor assemblies. The system shall provide 2-hour fire rating, tested to AST… | Nos | 102 | — | 10,771.53 | — | |
| 41 | C-AJ-2630 | CP 643N Firestop Collar,CP 637 Firestop Mortar | Providing UL-listed firestop system C-AJ-2630 for 4" PVC/CPVC/ABS/FRPP pipe penetrations through 2-1/2" thick concrete wall/floor assemblies. The system shall provide 2-hour fire rating, tested to AST… | Nos | 102 | — | 10,771.53 | — | |
| 42 | C-AJ-2647 | FS-ONE Max | Providing UL-listed firestop system C-AJ-2647 for 2" PVC/CPVC/RNC/ENT/PEX pipe penetrations through 3-1/2" thick concrete wall assemblies. The system shall provide 2-hour fire rating, tested to ASTM E… | Nos | 50 | 52 | 315.25 | 367.25 | |
| 43 | C-AJ-2647 | FS-ONE Max | Providing UL-listed firestop system C-AJ-2647 for 2" PVC/CPVC/RNC/ENT/PEX pipe penetrations through 3-1/2" thick concrete wall assemblies. The system shall provide 2-hour fire rating, tested to ASTM E… | nos | 50 | 52 | 315.25 | 367.25 | |
| 44 | C-AJ-2647 | FS-ONE Max | Providing UL-listed firestop system C-AJ-2647 for 2" PVC/CPVC/RNC/ENT/PEX pipe penetrations through 3-1/2" thick concrete wall assemblies. The system shall provide 2-hour fire rating, tested to ASTM E… | nos | 50 | 52 | 315.25 | 367.25 | |
| 45 | C-AJ-2647 | FS-ONE Max | Providing UL-listed firestop system C-AJ-2647 for 2" PVC/CPVC/RNC/ENT/PEX pipe penetrations through 3-1/2" thick concrete wall assemblies. The system shall provide 2-hour fire rating, tested to ASTM E… | nos | 50 | 52 | 315.25 | 367.25 | |
| 46 | C-AJ-2647 | FS-ONE Max | Providing UL-listed firestop system C-AJ-2647 for 2" PVC/CPVC/RNC/ENT/PEX pipe penetrations through 3-1/2" thick concrete wall assemblies. The system shall provide 2-hour fire rating, tested to ASTM E… | nos | 25 | 52 | 315.25 | 367.25 | |
| 47 | C-AJ-2677 | CP648E Wrap Strip, FS-ONE Max | Providing UL-listed firestop system C-AJ-2677 for Providing UL-listed firestop system C-AJ-2647 for 2" PVC/CPVC/RNC/ENT/PEX pipe penetrations through 3-1/2" thick concrete wall assemblies. The system … | Nos | 51 | — | 924.63 | — | |
| 48 | C-AJ-2700 | FS-ONE Max | Provide UL-listed firestop system for C-AJ-2700 1-1/4" PP pipe penetrations through 4-1/2" thick concrete wall assemblies and 6" thick floor assemblies, achieving a 2-hour F-rating per ASTM E814 / UL … | nos | 32 | 60 | 363.75 | 423.75 | |
| 49 | C-AJ-2700 | FS-ONE Max | Provide UL-listed firestop system for C-AJ-2700 1" PP pipe penetrations through 4-1/2" thick concrete wall assemblies and 6" thick floor assemblies, achieving a 2-hour F-rating per ASTM E814 / UL 1479… | Nos | 25 | — | 315.25 | — | |
| 50 | C-AJ-2700 | FS-ONE Max | Provide UL-listed firestop system for C-AJ-2700 3/4" PP pipe penetrations through 4-1/2" thick concrete wall assemblies and 6" thick floor assemblies, achieving a 2-hour F-rating per ASTM E814 / UL 14… | Nos | 19 | — | 266.75 | — | |
| 51 | C-AJ-2770 | CP 648E Wrap Strip,FS-ONE Max | Provide UL-listed firestop system C-AJ-2770 for 6" PP-R pipe through 4-1/2" thick Wall/floor, achieving 2 hour fire rating per ASTM E814 / UL 1479.Opening size shall be 8" with 1/2"-3/8" annular space… | Nos | 152 | — | — | — | |
| 52 | C-AJ-2770 | CP 648E Wrap Strip,FS-ONE Max | Provide UL-listed firestop system C-AJ-2770 for 4" PP-R pipe through 4-1/2" thick Wall/floor, achieving 2 hour fire rating per ASTM E814 / UL 1479.Opening size shall be 8" with 1/2"-3/8" annular space… | Nos | 102 | — | — | — | |
| 53 | C-AJ-2831 | CP 648E Wrap Strip,FS-ONE Max,Hilti Retaining Collar | Provide UL-listed firestop system C-AJ-2831 for 6" PP-R pipe through 4-1/2" thick wall/floor, achieving 2 hour fire rating per ASTM E814 / UL 1479. Opening size shall be 7" with 0"-1/2" annular space,… | Nos | 152 | — | 8,618.48 | — | |
| 54 | C-AJ-2885 | Hilti CFS-COS Firestop Composite Sheet, CP 619T Firestop Putty Roll, CP 617 Firestop Putty Pad or FS-ONE Max,CP 643N | Provide UL-listed firestop system C-AJ-2885 for 6" PVC/CPVC/RNC pipe through wall/floor thick 4-1/2", achieving 2-hour fire rating per ASTM E814 / UL 1479. Opening size shall be 30" with min 0" annula… | nos | 152 | 5,806.45 | 54,856.93 | 61,541.38 | |
| 55 | C-AJ-2885 | Hilti CFS-COS Firestop Composite Sheet, CP 619T Firestop Putty Roll, CP 617 Firestop Putty Pad or FS-ONE Max,CP 643N | Provide UL-listed firestop system C-AJ-2885 for 6" PVC/CPVC/RNC pipe through wall/floor thick 4-1/2", achieving 2-hour fire rating per ASTM E814 / UL 1479. Opening size shall be 30" with min 0" annula… | nos | 152 | 5,806.45 | 54,856.93 | 61,541.38 | |
| 56 | C-AJ-2885 | Hilti CFS-COS Firestop Composite Sheet, CP 619T Firestop Putty Roll, CP 617 Firestop Putty Pad or FS-ONE Max,CP 643N | Provide UL-listed firestop system C-AJ-2885 for 6" PVC/CPVC/RNC pipe through wall/floor thick 4-1/2", achieving 2-hour fire rating per ASTM E814 / UL 1479. Opening size shall be 30" with min 0" annula… | nos | 152 | 5,806.45 | 54,856.93 | 61,541.38 |